SIGNAL-20P APPLICATION
43
- 11 (ASPT)
- 12 (SIREN)
- 33 (ASPT-1)
- 34 (ASPT-A)
- 35 (ASPT-A1
Blocking of the relay control in case of auxiliary loop breaking impli-
cates that
- the relay doesn’t switch on in accordance with given tactics if the
loop has already broken
- if the breaking has happened when the relay was controlled it will
be returned to the initial status for given program
The relays controlled in accordance with programs 1…8, 11 and 33
will switch on when auxiliary loop has recovered but relays controlled in
accordance with programs 34 and 35 will keep switched off.
5.4.2 Type 12 auxiliary alarm loops
Type 12 auxiliary alarm loop five possible statuses are determined by
loop resistance threshold values, these values being shown below.
50
kOhm
loop resistance
0
status1
status2 status3 status4 status5
status threshold 4/5
status threshold 3/4
status threshold 2/3
status threshold 1/2
Figure 1. Statuses and status thresholds of programmable auxiliary loop
The loop resistance threshold values giving the boundary lines be-
tween statuses and status codes are user programmable. So the equip-
ment having several statuses and correspondingly several output contact
groups can be controlled by means of single loop including contact groups
into the alarm loops with additional resistances. These loops also can be
short or open failure monitored.
The device sound and light alarm and relay controlling are defined by
statuses this loop to enter. The programmable auxiliary loop status chang-
ing depends only on loop resistance changes and is not impacted by any
other factors or net controller commands. The resolving time when the
status is changing amounts 300 ms.